Q: I have read the White Paper 1: A Case for Lowering Component Level HBM/MM ESD Specifications and Requirements and found the ESD Control Programs and Resulting Data (Chapter 1, Page 20-23) particularly interesting.
Assuming a production environment with ESD flooring, footwear (and clothing), by the time a person walks to a workstation and sits down, the voltage of this persons should not exceed 500V (or even 100V as seen in Figure 3). That would mean even a seated operator in this case would not need to wear wrist strap, that theory would be correct right? After sitting down and this person sits on a stool (feet off the floor) with resistance to floor < 1.0×10exp9ohms, any HBM risk would be further reduced wouldn’t it?
A: Hello ****. Nice try. Even if you have an ESD flooring system and even if you have ESD footwear and even if you have an ESD task chair with ESD casters or an ordinary task chair with an ESD chair cover (very effective as well), ESD smock on… you STILL have to wear the wrist strap when seated at an ESD workstation.
�
The only time, per ANSI/ESD S20.20-2007 page 4, 8.2 Personnel Grounding, that personnel in the EPA (ESD Protected Area) should be without a wrist strap is when doing standing or walking about operations, and then two conditions must be met;
· “When the total resistance of the system (from the person, through the footwear and flooring to the grounding / Equipotential bonding system) is less than 3.5E7 Ω…”
· “When the total resistance of the system (from the person, through the footwear and flooring to the grounding / Equipotential bonding system) is greater than 3.5E7 Ω and less than 1.0E9 Ω and the BVG is less than 100 v per 97.2…”
�
This is what is said about seated personnel:
�
“When personnel are seated at ESD protective workstations, they shall be connected to the grounding / Equipotential bonding system via a wrist strap system.”
�
Hope this helps. I guess you could say redundancy is good in the realm of ESD. It’s the weak link in the chain that will cause an ESD event. If someone lifts their ESD footwear from the ESD flooring system while seated, they can tribocharge to above 100 volts. It takes only 0.3 seconds of charge time to exceed 20.20 requirements. If personnel is seated and getting up to go to break, it seems best to stand up, remove the wrist strap from the wrist, carefully set it down and walk away from the ESD workstation. Worst case is to take the wrist strap off while still seated, set it down, put your hand on the ESD workstation and near ESDS devices, then stand up out of the task chair before leaving the work station. Under proper conditions and with good bench mats, clean ESD floors, ESD task chairs, etc. in place, no ESD event. The problem with ESD events is that we cannot see, hear, feel them.�
�
The only alternative to not wearing a wrist strap while seated may be the used of a smock with a grounding coil cord attached to it. You can see the footnotes on the 20.20 document at the bottom of page 4 for further details.
�
We adhere to and meet or exceed requirements put forth in ANSI/ESD S20.20-2007 or IEC 61340-5-1, which assumes a target HBM of 100 volts and less.
Q: What should be the required Ground Rod-to-earth resistance? is it less than 2ohms or less than 25ohms?
A: I am going to consult my document on Grounding-For the Protection of Electrostatics Discharge Susceptible Items (ANSI/ESD S6.1-2005), an ESD Association standard. I am assuming that your inquiry is to provide the bonding and grounding for the prevention of ESD in an EPA (ESD Protected Area).
From the Main(s) service equipment or AC Mains, you have the Hot or Black conductor (Let’s assume AC Single Phase 120v) from the Circuit breaker panel, then you have the Neutral or white conductor coming from the Neutral bus, then you have the Equipment grounding conductor or green conductor. The black or Hot conductor comes from a circuit breaker and goes to an AC outlet receptacle. The white or Neutral conductor comes from a neutral bus which is bonded to an earth grounding electrode and goes to an AC outlet receptacle. The green conductor or equipment grounding conductor comes from a ground bus and is bonded to the metal chassis or conduit. The ground bus is then bonded to the Neutral bus. The common point ground or bus bar is connected or bonded to this ground connection, as is various other ESD technical elements (the grounding conductors or wires from wrist straps, worksurfaces, flooring or floor mats, tools, fixtures, storage units, carts, chairs, garments, etc).
The impedance of the equipment grounding conductor or receptacle ground to the common point ground or ESD technical element shall not be greater than 1 ohm (Ω). I see no mention of 2 ohms (Ω) in this document, although it is noted that the ground resistance values objectives vary from industry to industry. The telecommunications industry has often used 5 ohms or less as their value for grounding and bonding. The goal in grounding resistance values is to achieve the lowest ground resistance value possible. The National Electrical Code defines a ground as: “a conductive connection, whether intentional or accidental between an electrical circuit or equipment and the earth, or to some conducting body that serves in place of the earth.” The purpose of a ground besides the protection of people and equipment is to provide a safe path for the dissipation of Fault Currents, Lightning Strikes, Static Discharges, EMI and RFI signals and Interference.
The reference to 25 ohms refers to facilities with AC Equipment Ground and Auxiliary Ground (A separate supplemental grounding conductor for use other than general equipment grounding) per ANSI/ESD S6.1-2005 6.3.2. The auxiliary ground shall be bonded to the AC equipment ground when possible. The AC equipment and the ESD technical elements might be at different potentials. The auxiliary ground needs to be bonded to the equipment ground to ensure that there is no difference in electrical potential between the two systems.
Q: We have an ESD tile floor in our testing lab. During a recent AS9100 audit we were asked why we don’t use wrist straps. Since our ISO9100 & 2 certified calibration provider only uses them when they have to certify the repair of a system and we don’t do that do we need more than the flooring? (booties, straps, etc.)
A: The answer to your question is, YES. In accordance to EOS/ESD standards, an ESD floor in conjunction with Heel Grounders, ESD Booties, ESD Foot Wear does NOT take the place of using Personnel grounded Wrist Straps at the workstation. So the basic ESD program would include the technician wearing a Wrist Strap.
Protective personnel grounding products such as; heel straps, booties and shoes working in conjunction with an ESD floor are designed for processes within your ESD program where the technician has to be mobile within an ESDPA, (ESD Protected Area) where the electrostatic sensitive device is not protected in an ESD protective container or shielded in some manner, e.g. ESD Bag, Bin, Tote, Box, Tray, Container, etc.
If your process has technical personnel setting or standing at a workstation they DO require grounding via a Wrist Strap. So one doesn’t necessarily take the place of the other, and both may be required depending on your personnel and their mobility throughout the plant.
If your technical staff removes their wrist strap to transport an ESD sensitive device or component outside the ESD protected area, the device also needs to be shielded as well as the technician being properly outfitted with ESD shoes, booties or heel straps. Within the ESDPA, they do require the additional shielding protection of the device, but it is always a good idea when practical.
I hope this helps address your question, please let us know if we can be of further assistance with any ESD questions or ESD protective product requirements you and your team may be sourcing.